Specification

GENERAL

The 15 - 130 Ton (53 - 457 kW) YCUL Condensing Unit

Models are shipped complete from the factory ready for

field installation.

The unit is pressure-tested, evacuated and given a nitro-

gen holding charge and includes an initial oil charge (R-

22 or HFC-407C refringerant supplied by others). After

assembly, a operational test is performed to assure that

each control device operates correctly.

The unit structure is heavy-gauge, galvanized steel.

This galvanized steel is coated with baked-on powder

paint, which, when subjected to ASTM B117 500 hour,

salt spray testing, yields a minimum ASTM 1654 rating

of “6”. Units are designed in accordance with NFPA 70

(National Electric Code), ASHRAE/ANSI 15 Safety code

for mechanical refrigeration, and are cETL listed. All units

are produced at an ISO 9000-registered facility.

COMPRESSORS

The chiller has suction-gas cooled, hermetic, scroll

compressors. The compressors incorporate a compli-

ant scroll design in both the axial and radial direction.

All rotating parts of the compressors are statically and

dynamically balanced. A large internal volume and oil

reservoir provides greater liquid tolerance. Compressor

crankcase heaters are also included for extra protection

against liquid migration.

CONDENSER

Coils – Fin and tube condenser coils of seamless, inter-

nally-enhanced, high-condensing-coefficient, corrosion

resistant copper tubes are arranged in staggered rows,

mechanically expanded into aluminum fins. Integral

subcooling is included. The design working pressure of

the coil is 450 PSIG (31 bar).

Fans – The condenser fans are composed of corrosion-

resistant aluminum hub and glass-fiber-reinforced

polypropylene composite blades molded into a low

noise airfoil section. The are designed for maximum

efficiency and are statically and dynamically balanced

for vibration free operation. They are directly driven

by independent motors, and positioned for vertical air

discharge. The fan guards are constructed of heavy-

gauge, rust-resistant, coated steel. All blades are

statically and dynamically balanced for vibration-free

operation.

Motors – The fan motors are Totally Enclosed Air-Over,

squirrel-cage type, current protected. They feature

ball bearings that are double-sealed and permanently

lubricated.

REFRIGERANT CIRCUIT

One (YCUL0016-0040) or two (YCUL0046-0130) inde-

pendent refrigerant circuits will be finished on each unit.

All unit piping will be copper, with brazed joints. The

liquid line will include a field connection shutoff valve with

charging port located on each condenser circuit. Suc-

tion line connections are provided on each refrigeration

circuit. A filter drier and sight glass are shipped loose

for field installation on each refrigerant circuit.

All expansion valves, liquid line solenoid valves, refriger-

ant, and refrigerant field piping are supplied by others.