Installation Instructions

975-0301-01-01

19

3. Connect the incoming negative (-) black cable from each of the loads to the

negative DC bus.

4. Connect the incoming positive (+) red cable from each of the loads to the

positive DC bus.

5. Install fuses for the DC loads and the DC battery. The bottom four DC fuses

are for the battery. Fuses for DC loads should be Littelfuse Type 257 or
equivalent and the maximum allowed fuse for the DC loads is 20 A.

6. Connect the incoming negative (-) black cable from the battery to the negative

DC battery lug.

7. Connect the incoming positive (+) red cable from the battery to the positive

DC battery lug.

8. Tighten the clamp screws on the strain relief to secure the DC wires.

Important:

You may remove the PCB with the positive DC bus and fuse holders (by

removing the three screws) for ease of connection. Keep the screws for reconnecting the
PCB. See Figure 13.

Figure 13 DC PCB Removal

Remove these
three screws

Figure 14 Connecting DC to the Panel

Positive DC bus

DC fuses

DC Knockouts

Negative DC bus

Positive DC
battery lug

Negative DC
battery lug