York BQ 036 User Manual

Page 24

Advertising
background image

036-21508-005-A-0305

24

Unitary Products Group

TABLE 12: STATIC RESISTANCES

TABLE 13: ELECTRIC HEATER CFM LIMITATIONS

1000

1200

1400

1600

1800

2000

2200

2400

2600

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

5-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

BOTTOM DUCT CONNECTIONS

1

ELECTRIC

HEATERS

1

RESISTANCE, IWG

CFM

DESCRIPTION

ECONOMIZER

1, 2

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

5

7

10

15

20

30

208/230-1-60

1100

1100

1200

1200

1300

-

208/230-3-60

1100

1100

1200

1200

1300

-

460-3-60

-

1100

1200

1200

1300

-

575-3-60

-

-

1200

1200

1300

-

208/230-1-60

1300

1300

1300

1300

1300

-

208/230-3-60

1300

1300

1300

1300

1300

-

460-3-60

-

1300

1300

1300

1300

-

575-3-60

-

-

1300

1300

1400

-

208/230-1-60

1600

1600

1600

1600

1600

1600

208/230-3-60

1600

1600

1600

1600

1600

1600

460-3-60

-

1600

1600

1600

1600

1600

575-3-60

-

-

1600

1600

1600

1800

3

4

5

MINIMUM SUPPLY AIR CFM

HEATER SIZE NOMINAL KW

VOLTAGE

UNIT MODEL SIZE NOMINAL

TONS

Advertising
This manual is related to the following products: