TABLE 15: ELECTRICAL DATA (BASIC UNIT)

MODEL

BHP

POWER

SUPPLY

VOLTAGE

LIMITATIONS

1

COMPRESSOR

OUTDOOR

FAN

MOTOR,

FLA

SUPPLY AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX

FUSE

SIZE,

AMPS

2

MAX.

HACR

BREAKER

SIZE,

AMPS

UNIT

POWER

FACTOR

TRANSFORMER

SIZE (VA)

MIN.

MAX.

RLA

LRA

024

208/230-1-60

187

253

9.3

57.0

1.1

5.0

17.7

25

25

0.96

40

030

208/230-1-60

187

253

15.0

72.5

1.1

5.0

24.9

35

35

0.96

40

208/230-3-60

187

253

10.0

63.0

1.1

5.0

18.6

25

25

0.96

75

460-3-60

414

504

5.0

31.0

0.6

5.0

11.9

15

15

0.96

75

036

208/230-1-60

187

253

17.2

94.0

1.1

7.3

29.9

45

45

0.96

40

208/230-3-60

187

253

11.4

78.0

1.1

7.3

22.7

30

30

0.96

75

460-3-60

414

504

5.7

40.0

0.6

7.3

15.4

20

20

0.96

75

042

208/230-1-60

187

253

20.0

104.0

1.1

7.3

33.4

50

50

0.96

40

208/230-3-60

187

253

13.9

88.0

1.1

7.3

25.8

35

35

0.96

75

460-3-60

414

504

6.4

44.0

0.6

7.3

16.1

20

20

0.96

75

048

208/230-1-60

187

253

23.4

126.0

1.5

7.3

38.1

60

60

0.96

40

208/230-3-60

187

253

13.0

93.0

1.5

7.3

25.1

35

35

0.96

75

460-3-60

414

504

6.4

46.5

0.8

7.3

16.3

20

20

0.96

75

1.

Rated in accordance with ARI Standard 100, utilization range ìAî.

2.

Dual element, time delay type.

ELECTRIC HEAT

CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE KW CAP. MULTIPLIER

240

208

230

0.75

0.92

480

460

0.92