9model solid fuel cooker, Pre-installation checks, Additional ventilation – Yeoman YM-CKWDBL-R User Manual

Page 9

Advertising
background image

9

Model

Solid fuel cooker

Additional

ventilation

mm

2

1375

cm

2

13.75

sq. inch

2.125

2.2 Extractor fans or cooker hoods should not be placed in

the same room or space as the appliance.

2.3 If any of these checks reveal problems do not

proceed with the fitting of the appliance until they

have been rectified.

PRE-INSTALLATION CHECKS

1.11 Where a hearth, fireplace, flue or chimney is provided

or extended (including cases where a flue is provided as

part of refurbishment work), information essential to

the correct appliance and use of these should be

permanently posted in the building, to meet

Requirement J4 of the Building Regulations (England

and Wales), F3.12 (Scotland).

2. Additional Ventilation

2.1 Additional ventilation will be required to comply with

the requirements of the Building Regulations. This

should be provided using a permanently open air vent,

of the size listed, which is positioned so that it is not

liable to be blocked both inside and outside the

building.