TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE

BLOWER

SPEED,

RPM

MOTOR

PULLEY
(TURNS

OPEN)*

AIRFLOW

1.77 m

3

/s

2.07 m

3

/s

2.36 m

3

/s

2.66 m

3

/s

2.95 m

3

/s

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

ESP

(Pa)

Output

(kW)

Input

(kW)

845

6.0

273

1.56

1.8

223

1.79

2.2

198

2.09

2.5

174

2.38

2.9

149

2.68

3.2

885

5.0

322

1.64

1.9

273

1.94

2.3

223

2.24

2.7

198

2.53

3.1

174

2.83

3.4

925

4.0

372

1.71

2.1

322

2.01

2.5

248

2.38

2.9

223

2.68

3.3

-

-

-

960

3.0

422

1.79

2.2

347

2.16

2.6

298

2.46

3.0

248

2.83

3.4

-

-

-

1000

2.0

446

1.86

2.3

397

2.24

2.7

347

2.61

3.2

-

-

-

-

-

-

1040

1.0

496

1.94

2.4

446

2.38

2.9

372

2.76

3.3

-

-

-

-

-

-

DOWNFLOW DUCT APPLICATIONS (m /s) - B*CH180 UNIT

3

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

AIRFLOW

3750 CFM

4380 CFM

5000 CFM

5630 CFM

6250 CFM

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

ESP

(iwg)

Output

(bhp)

Input

(kW)

845

6.0

1.1

2.1

1.8

0.9

2.4

2.2

0.8

2.8

2.5

0.7

3.2

2.9

0.6

3.6

3.2

885

5.0

1.3

2.2

1.9

1.1

2.6

2.3

0.9

3.0

2.7

0.8

3.4

3.1

0.7

3.8

3.4

925

4.0

1.5

2.3

2.1

1.3

2.7

2.5

1.0

3.2

2.9

0.9

3.6

3.3

-

-

-

960

3.0

1.7

2.4

2.2

1.4

2.9

2.6

1.2

3.3

3.0

1.0

3.8

3.4

-

-

-

1000

2.0

1.8

2.5

2.3

1.6

3.0

2.7

1.4

3.5

3.2

-

-

-

-

-

-

1040

1.0

2.0

2.6

2.4

1.8

3.2

2.9

1.5

3.7

3.3

-

-

-

-

-

-

NOTES: 1. Blower performance includes fixed outdoor air, standard unit filters, a dry indoor coil and no electric heat.

2. Refer to Table 5 for additional static resistances.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

*

Do NOT close the pulley below 1 turn open.

DOWNFLOW DUCT CONNECTIONS (CFM) - B*CH180 UNIT