035-18895-000-A-0902

Unitary Products Group

15

SECURE OWNER'S APPROVAL

: When the system is functioning properly, secure the owner's approval. Show him the

location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature
settings within the limitations of the system.

FIG. 11 - AMBIENT MODIFIED TIME/TEMPERATURE CONTROL

T1 - 50 MINUTE SETTING

T2 - 80 MINUTE SETTING

T3 - 110 MINUTE SETTING
(Factory Set Point)

SHORTING PEGS TO
OVERRIDE TIMER
FOR SERVICE

MOVABLE JUMPER
WIRE TO CHANGE
DEFROST TIMER

NORMAL MAINTENANCE

CAUTION: Prior to any of the following maintenance proce-

dures, shut off all power to the unit to prevent per-
sonal injury.

FILTERS - Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace permanent
type with disposable. The dimensional size of the replacement
filter must be the same as the replaced filter.

MOTORS

Outdoor fan motors are permanently lubricated and require no
maintenance.

Indoor Blower Motor and Drive - The indoor blower motor
features ball-bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the
life of components but is optional.

CAUTION: Damage can occur if the bearings are overlubri-

cated. Use grease sparingly.

WARNING:

Perform all maintenance operations on the blower motor with
power disconnected from the unit. Do not attempt to lubricate
bearings with the unit in operation.

On an annual basis, check the motor for accumulations of dust,
etc. that may block the cooling slots in the motor shell. Check
for loose, damaged or misaligned drive components. Check
that all mounting bolts are tight. Replace defective parts as
required.

If desired, every three years remove both pipe plugs at each
end shell and clean out any hardened grease or foreign matter.
Replace one plug on each end with a clean grease fitting. Using
a low pressure grease gun, pump grease (Chevron SR1-2 or
equivalent) into the bearing cavity until new grease shows at
the open port. Do not over-lubricate. Run the motor for ten
minutes until excess grease is purged from the cavity. Replace
the plugs.

OUTDOOR COIL - Dirt should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit. Cleaning
should be as often as necessary to keep coil clean. Use a
brush, vacuum cleaner attachment, or other suitable means. If
water is used to clean coil, be sure power to the unit is shut off
prior to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil

fins are not damaged.

Do not permit the outdoor air discharge to be obstructed by
overhanging structures or shrubs.