FIELD WIRING CONNECTION - COOLING ONLY

FIELD WIRING CONNECTION - WITH HEATER KIT

ELECTRICAL DATA - 3

- (SINGLE SOURCE POWERSUPPLY) - COPPER WIRE

Models

Heater Models

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

1

Amps

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

75°C Wire Size - AWG

208V

240V

208V

240V

208V

240V

F4FP024H06T2*

2HK06501025B

41.2

46.5

45

50

8

8

F4FP030H06T2*

2HK06501025B

42.2

47.4

45

50

8

8

2HK06501525B

42.2

47.4

45

50

8

8

F4FP036H06T2*

2HK06501025B

43.1

48.2

45

50

8

8

2HK06501525B

43.1

48.2

45

50

8

8

F4FP040H06T2*

2HK06501025B

42.2

47.4

45

50

8

8

2HK06501525B

42.2

47.4

45

50

8

8

F4FP042H06T2*

2HK06501025B

44.2

49.1

45

50

8

8

2HK06501525B

44.2

49.1

45

50

8

8

F4FP045H06T2*

2HK06501025B

42.8

47.9

45

50

8

8

2HK06501525B

42.8

47.9

45

50

8

8

F5FP048H06T2*

2HK06501025B

48.3

53.9

50

60

8

6

2HK06501525B

48.3

53.9

50

60

8

6

F5FP060H06T2*

2HK06501025B

48.3

53.9

50

60

8

6

2HK06501525B

48.3

53.9

50

60

8

6

F4FV060H06T2*

2HK06501025B

48.6

52.9

50

60

8

6

2HK06501525B

48.6

52.9

50

60

8

6

THERMOSTAT

OUTDOOR
UNIT

R

Y

G

W

R

Y

G

W2 W1

O

C

FAN
COIL
UNIT

*

*

N OT REQUIRED ON 2 OR 5KW

THERMOSTAT

OUTDOOR
UNIT

R

Y

G

W

R

Y

G

W2 W1

O

C

FAN
COIL
UNIT