York F*FP User Manual

Page 5

Advertising
background image

295421-YTG-B-0707

Unitary Products Group

5

EXTENDED AIR FLOW DATA

1

FOR 208 VOLT - HEAT PUMP MODELS

1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

Models

Blower Motor

Speed

208 Volt

CFM @ External Static Pressure - IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

F4FP024H06T2*

High

855

819

779

752

698

657

596

531

452

360

Med.

760

733

706

670

634

589

535

472

395

310

Low

585

567

545

518

486

457

405

344

257

142

F4FP030H06T2*

High

1143

1089

1035

977

914

851

776

692

581

451

Med.

941

936

895

837

770

724

643

562

445

328

Low

770

738

702

662

612

561

495

402

300

171

F4FP036H06T2*

High

1235

1179

1125

1058

1008

947

885

804

701

580

Med.

1080

1035

990

936

887

840

791

716

640

528

Low

954

914

873

833

774

728

666

595

515

408

F4FP040H06T2*

High

1143

1089

1035

977

914

851

776

692

581

451

Med.

941

936

895

837

770

724

643

562

445

328

Low

770

738

702

662

612

561

495

402

300

171

F4FP042H06T2*

High

1400

1418

1350

1278

1215

1145

1073

991

897

784

Med.

1314

1266

1197

1135

1071

1012

947

864

758

625

Low

1125

1080

1040

990

945

901

838

766

676

568

F4FP045H06T2*

High

1418

1382

1328

1251

1179

1120

1032

927

807

661

Med-high

1238

1184

1130

1067

999

936

850

763

659

545

Med-low

1089

1044

999

945

882

829

760

663

576

480

Low

932

891

846

801

743

693

628

554

472

389

F5FP048H06T2*

High

2209 2140 2093 2000 1939 1864

1746

1724

1655

1587

Med

High

1945 1906 1871 1819 1784 1741

1667

1640

1595

1550

Med

1739 1690 1640 1602 1559 1516

1470

1431

1387

1343

Med

Low

1506 1464 1415 1369 1325 1283

1238

1193

1139

1100

Low

1301 1248 1197 1151 1095 1054

1005

958

909

860

F5FP060H06T2*

High

2134 2124 2052 1979 1861 1756

1639

1597

1512

1427

Med

High

1916 1875 1838 1777 1744 1671

1594

1584

1537

1490

Med

1716 1671 1613 1569 1523 1475

1429

1384

1337

1290

Med

Low

1494 1435 1390 1341 1284 1241

1194

1139

1087

1036

Low

1276 1223 1168 1115 1068 1009

965

902

847

792

F4FV060H06T2*

High

2057

1976

1895

1814

1728

1661

1593

1517

1431

1337

Med.

1913

1818

1719

1625

1535

1437

1342

1247

1152

1057

Low

1490

1445

1395

1350

1305

1258

1194

1120

1038

946

NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.

APPLICATION FACTORS-RELATED CFM VS. ACTUAL CFM

% Of Rated Airflow

80%

90%

RATED CFM

110%

120%

Capacity Factor

0.96

0.98

1.00

1.02

1.03

Advertising