AIR FLOW DATA

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

40,000 INPUT - 3 Ton

60,000 INPUT - 3 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

COOL

Tap

ADJ

Tap

1340

995

38.0

28.2

1330

900

37.7

25.5

A B

1205

885

34.1

25.1

1130

800

32.0

22.7

B B

1255

920

35.6

26.1

1220

850

34.6

24.1

A A

1150

835

32.6

23.7

1040

730

29.4

20.7

B A

1170

855

33.2

24.2

1120

770

31.7

21.8

A C

1025

755

29.0

21.4

920

650

26.1

18.4

C B

1045

780

29.6

22.1

950

660

26.9

18.7

B C

835

625

23.7

17.7

740

540

21.0

15.3

D B

950

705

26.9

20.0

860

610

24.4

17.3

C A

785

590

22.2

16.7

690

540

19.5

15.3

D A

865

665

24.5

18.8

790

570

22.4

16.1

C C

725

605

20.5

17.1

630

530

17.8

15.0

D C

80,000 INPUT - 3 Ton

80,000 INPUT - 4 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

COOL

Tap

ADJ

Tap*

1310

890

37.1

25.2

1660

1110

47.0

31.4

A B

1100

740

31.2

21.0

1550

1050

43.9

29.7

B B

1220

830

34.6

23.5

1610

1070

45.6

30.3

A A

1000

670

28.3

19.0

1440

960

40.8

27.2

B A

1090

720

30.9

20.4

1470

990

41.6

28.0

A C

900

610

25.5

17.3

1370

920

38.8

26.1

C B

880

610

24.1

17.3

1290

850

36.5

24.1

B

C

680

510

19.3

14.4

1130

790

32.0

22.4

D

B

810

580

22.9

16.4

1230

850

34.8

24.1

C

A

630

500

17.8

14.2

1050

720

29.7

20.4

D

A

730

530

20.7

15.0

1110

760

31.4

21.5

C

C

590

500

16.7

14.2

950

660

26.9

18.7

D C

100,000 INPUT - 5 Ton

120,000 INPUT - 5 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

COOL

Tap

ADJ

Tap*

2210

1480

62.6

41.9

2280

1510

64.6

42.8

A B

1780

1180

50.4

33.4

1860

1190

52.7

33.7

B B

2040

1350

57.8

38.2

2090

1370

59.2

38.8

A A

1620

1050

45.9

29.7

1630

1060

46.2

30.0

B A

1840

1250

52.1

35.4

1880

1250

53.2

35.4

A C

1560

1010

44.2

28.6

1620

1030

45.9

29.2

C B

1470

940

41.6

26.6

1500

960

42.5

27.2

B

C

1370

890

38.8

25.2

1410

880

39.9

24.9

D

B

1460

930

41.3

26.3

1490

920

42.2

26.1

C

A

1250

790

35.4

22.4

1290

790

36.5

22.4

D

A

1310

810

37.1

22.9

1360

840

38.5

23.8

C

C

1090

690

30.9

19.5

1140

690

32.3

19.5

D C

HIGH / LOW HEAT CFM

40,000 INPUT - 3 Ton

60,000 INPUT - 3 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

HEAT

Tap

ADJ

Tap*

1045

740

29.6

21.0

1110

710

31.4

20.1

A Any

905

645

25.6

18.3

960

640

27.2

18.1

B Any

825

595

23.4

16.8

870

600

24.6

17.0

C Any

765

590

21.7

16.7

830

570

23.5

16.1

D Any

80,000 INPUT - 3 Ton

80,000 INPUT - 4 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

HEAT

Tap

ADJ

Tap*

1330

880

37.7

24.9

1490

990

42.2

28.0

A Any

1180

810

33.4

22.9

1350

900

38.2

25.5

B Any

1100

730

31.2

20.7

1220

820

34.6

23.2

C Any

1010

670

28.6

19.0

1120

770

31.7

21.8

D Any

100,000 INPUT - 5 Ton

120,000 INPUT - 5 Ton

JUMPER SETTINGS

CFM m³/min CFM m³/min

High Low High Low High Low High Low

HEAT

Tap

ADJ

Tap*

1880

1230

53.2

34.8

2150

1420

60.9

40.2

A Any

1670

1080

47.3

30.6

1930

1290

54.7

36.5

B Any

1530

980

43.3

27.8

1850

1190

52.4

33.7

C Any

1430

900

40.5

25.5

1660

1070

47.0

30.3

D Any

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From
0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
The ADJ “D” tap should not be used.