FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE: The filter pressure drop values in the “Filter Perfor-
mance” table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.

* Washable Fibers are the type supplied with furnace (if supplied.

APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.

Select the filter type.

2.

Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.

3.

Determine the External System Static Pressure (ESP)
without the filter.

4.

Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.

5.

If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corre-
sponds to the intersection of the ESP column and Model/
Blower Speed row.

BLK

WHT

GRN

BLK (HOT)

WHT (NEUTRAL)

GRN

NOMINAL
120 VOLT

LINE WIRING CONNECTIONS

SINGLE STAGE HEATING

THERMOSTAT CONNECTIONS

SINGLE STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y1

C

R

G

C
COMMON T’STAT CONNECTION

Y2

Y1

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y
C

R

G

C

COMMON T’STAT CONNECTION

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W1
W2

G

Y2

R

G

COMMON T’STAT CONNECTION

Y1

Y1

W1/W

C

C

W2

Y/Y2

TWO-STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

Airflow Range

Minimum Opening Size

Filter Type

Disposable

WASHABLE FIBER*

Pleated

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.

Sq. in.

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

0 - 750

230

0.01

2.5

0.01

2.5

0.15

37

751 - 1000

330

0.04

10

0.03

7.5

0.20

50

1001 - 1250

330

0.08

20

0.07

17

0.20

50

1251 - 1500

330

0.08

20

0.07

17

0.25

62

1501 - 1750

380

658

0.14

35

0.08

20

0.13

32

0.06

15

0.30

75

0.17

42

1751 - 2000

380

658

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42

2001 & Above

463

658

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42