Step B

Setting the Amperage Trigger Level

1B. Press the SELECT button until the Amperage LED (

A

) is illuminated.

2B. Press the SELECT and RESET buttons simulataniously until the LED

display flashes.

3B. Press the RESET button until the display indicates the desired

amperage.

4B. Press SELECT button to accept.

The selectable amperage values are from 1 to 99 amps.

The TM500A is now setup to trigger the CHARGED indicator LED (

)

when the voltage level equals or exceeds the value programmed in Step A
and the amperage level falls below the value programmed in Step B. When
these parameters are met, the CHARGED indicator LED flashes approximately
every four seconds. Whenever the current goes negative (discharge) the
timer resets to zero. The CHARGED indicator must be manually reset to turn
it OFF.

Setting Parameters (continued)

CHARGED Indicator Setup (continued)

Figure 3-7

Setting the CHARGED Indicator Voltage Level

Figure 3-8

Trigger on Voltage and Amperage

14.4

Set Voltage Level

1A

4A

2A

Voltage LED

Illuminates to Indicate

the Voltage Function

is Selected

3A

44A

Set Amperage

Amperage LED

Illuminates to Indicate the

Amperage Function is

2B

3B

4B

1B