Rs*048 — 1600 cfm, Performance data – York YK145.00-EG4 User Manual

Page 16

Advertising
background image

16

Johnson Controls

Technical Guide: YK145.00-EG4 (309)

Water Source Heat Pumps

PERFORMANCE DATA

RS*048 — 1600 CFM

EWT (F)

GPM

WPD

COOLING

HEATING

PSI

FT

TC

SC

kW

HR

EER

HTG

kW

HE

LAT (F)

COP

20

12.0

15.1

34.9

30.5

3.32

19.1

86

2.8

30

6.0

4.4

10.1

61.3

42.9

2.33

69.3

26.3

33.4

3.30

3.3

88

3.0

9.0

8.5

19.5

62.2

43.4

2.29

70.0

27.2

35.6

3.32

3.3

89

3.1

12.0

13.2

30.4

62.8

43.5

2.27

70.5

27.7

36.7

3.34

3.3

89

3.2

40

6.0

3.8

8.8

58.0

41.5

2.46

66.4

23.6

39.8

3.33

3.6

91

3.5

9.0

7.4

17.0

58.8

41.9

2.40

67.0

24.5

41.5

3.38

3.6

92

3.6

12.0

11.5

26.5

59.4

42.2

2.37

67.5

25.1

43.6

3.55

3.6

93

3.6

50

6.0

3.4

7.8

55.4

39.9

2.69

64.6

20.6

44.2

3.63

3.6

94

3.6

9.0

6.5

15.0

56.5

40.4

2.62

65.4

21.6

45.8

3.66

3.7

95

3.7

12.0

10.1

23.4

57.6

40.9

2.50

66.1

23.0

47.4

3.68

3.7

95

3.8

60

6.0

2.9

6.8

51.1

37.6

2.97

61.2

17.2

51.1

3.62

3.6

97

4.1

9.0

5.6

13.0

51.7

37.7

2.82

61.3

18.3

53.1

3.65

3.7

98

4.3

12.0

8.8

20.3

52.3

38.0

2.73

61.6

19.2

54.6

3.70

3.7

99

4.3

70

6.0

2.7

6.2

49.8

37.1

3.39

61.4

14.7

58.8

3.84

3.8

100

4.5

9.0

5.2

12.0

50.2

36.9

3.26

61.3

15.4

59.8

3.87

3.9

101

4.5

12.0

8.1

18.7

50.8

37.1

3.11

61.4

16.3

61.3

3.90

3.9

102

4.6

80

6.0

2.4

5.5

48.1

37.2

3.98

61.7

12.1

63.2

4.05

4.1

103

4.6

9.0

4.6

10.6

48.6

37.3

3.78

61.5

12.9

64.6

4.11

4.1

105

4.6

12.0

7.1

16.5

49.4

37.7

3.66

61.9

13.5

67.2

4.16

4.2

106

4.7

90

6.0

2.1

4.9

46.4

36.7

4.51

61.8

10.3

70.3

4.28

4.3

107

4.8

9.0

4.1

9.4

47.2

37.1

4.26

61.7

11.1

72.4

4.32

4.3

108

4.9

12.0

6.3

14.6

47.7

37.3

4.12

61.8

11.6

73.3

4.34

4.3

109

4.9

100

6.0

1.9

4.3

43.6

36.4

5.05

60.8

8.6

9.0

3.6

8.4

45.0

37.3

4.76

61.2

9.5

12.0

5.6

13.0

45.9

37.9

4.59

61.6

10.0

110

6.0

1.7

3.9

39.9

33.9

5.70

59.4

7.0

9.0

3.2

7.5

41.3

34.8

5.36

59.6

7.7

12.0

5.0

11.7

42.2

35.0

5.16

59.8

8.2

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT
Tabulated data does not include ARI/ISO corrections for fan and pump power.
All capacities are expressed in MBH.
Insulated water circuit is recommended for operation below 60F EWT.
See performance correction tables for conditions beyond what is listed.
Extrapolation is not permissible.
Shaded areas indicate conditions where operation is not recommended.