Ari/iso performance data – York YK145.00-EG4 User Manual

Page 7

Advertising
background image

Johnson Controls

7

Water Source Heat Pumps

Technical Guide: YK145.00-EG4 (309)

ARI/ISO PERFORMANCE DATA

PERFORMANCE DATA - ARI/ISO 13256-1 WATER LOOP CONDITIONS*

Unit Model

Flow Rate

(USGPM)

Air Flow

(SCFM)

Cooling

Capacity (Btuh)

EER

Heating

Capacity (Btuh)

COP

007

1.8

260

6,800

12.5

8,700

4.5

009

2.4

320

8,900

12.4

11,600

4.4

012

3.0

400

12,400

12.2

15,600

4.2

018

4.8

640

19,100

13.2

23,400

4.5

024

6.0

800

24,600

13.5

29,300

4.4

030

7.8

1000

29,800

13.3

35,300

4.5

036

9.0

1200

36,200

13.0

45,100

4.6

042

10.4

1400

42,700

12.7

50,600

4.4

048

12.0

1600

48,300

13.1

57,200

4.5

060

15.0

2000

60,500

13.4

70,800

4.6

070

17.5

2200

67,700

12.9

79,500

4.3

*Water Loop capacities are rated at 86°F EWT Cooling, 68°F EWT Heating.

PERFORMANCE DATA - ARI/ISO 13256-1 GROUND WATER CONDITIONS*

Unit Model

Flow Rate

(USGPM)

Air Flow

(SCFM)

Cooling

Capacity (Btuh)

EER

Heating

Capacity (Btuh)

COP

007

1.8

260

7,700

18.4

6,900

3.9

009

2.4

320

10,100

18.3

9,100

3.8

012

3.0

400

14,200

18.1

12,900

3.6

018

4.8

640

22,900

20.2

18,800

3.9

024

6.0

800

28,700

20.8

23,600

3.8

030

7.8

1000

33,600

20.0

29,100

3.8

036

9.0

1200

39,800

18.8

37,200

3.9

042

10.4

1400

45,800

19.1

42,300

3.9

048

12.0

1600

52,500

19.3

47,400

3.8

060

15.0

2000

66,400

19.8

59,000

4.0

070

17.5

2200

73,600

18.7

66,800

3.8

*Ground Water capacities are rated at 59°F EWT Cooling, 50°F EWT Heating.

PERFORMANCE DATA - ARI/ISO 13256-1 GROUND LOOP CONDITIONS*

Unit Model

Flow Rate

(USGPM)

Air Flow

(SCFM)

Cooling

Capacity (Btuh)

EER

Heating

Capacity (Btuh)

COP

007

1.8

260

7,100

14.6

5,500

3.4

009

2.4

320

9,300

14.5

6,900

3.3

012

3.0

400

13,000

14.3

10,200

3.1

018

4.8

640

20,600

15.7

13,900

3.4

024

6.0

800

26,400

16.1

17,400

3.3

030

7.8

1000

31,100

15.3

22,500

3.3

036

9.0

1200

37,500

14.8

28,600

3.3

042

10.4

1400

43,900

14.6

32,300

3.4

048

12.0

1600

49,800

15.0

37,800

3.3

060

15.0

2000

62,900

15.6

47,200

3.5

070

17.5

2200

70,100

14.7

52,400

3.3

*Ground Loop capacities are rated at 77°F EFT Cooling, 32°F EFT Heating.

NOTE:
1) All Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
2) All Heating capacities based upon 68°F DB, 59°F WB entering air temperature.

Advertising