13 supply air blower performance (bp060, Belt drive) - bottom duct application – York BP 036 User Manual

Page 20

Advertising
background image

255027-YTG-B-0507

20

Unitary Products Group

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (BP060 BELT DRIVE) - BOTTOM DUCT APPLICATION

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

1

0.2

0.3

0.4

0.5

0.6

0.7

RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000

-

-

-

-

-

-

-

-

-

-

-

-

862

453

0.49

901

498

0.53

1100

-

-

-

-

-

-

-

-

-

-

-

-

883

494

0.53

922

539

0.58

1200

-

-

-

-

-

-

-

-

-

866

489

0.53

904

536

0.58

943

581

0.62

1300

-

-

-

-

-

-

850

488

0.52

889

535

0.57

928

581

0.62

967

627

0.67

1400

-

-

-

836

491

0.53

875

537

0.58

913

584

0.63

952

631

0.68

991

676

0.73

1500

-

-

-

862

545

0.58

901

591

0.63

940

638

0.68

978

685

0.73 1017

730

0.78

1600

851

559

0.60

890

604

0.65

928

650

0.70

967

697

0.75 1006

744

0.80 1045

789

0.85

1700

880

624

0.67

919

668

0.72

958

714

0.77

996

761

0.82 1035

808

0.87 1074

853

0.92

1800

911

694

0.74

949

738

0.79

988

785

0.84 1027

832

0.89 1066

878

0.94 1105

923

0.99

1900

942

770

0.83

981

814

0.87 1020

860

0.92 1059

907

0.97 1097

954

1.02 1136

999

1.07

2000

976

851

0.91 1014

895

0.96 1053

941

1.01 1092

989

1.06 1130

1035

1.11 1169

1080

1.16

2100

1010

938

1.01 1049

982

1.05 1087

1028

1.10 1126

1075

1.15 1165

1122

1.20 1204

1167

1.25

2200

1046

1030

1.11 1084

1075

1.15 1123

1121

1.20 1162

1168

1.25 1200

1215

1.30

-

-

-

2300

1082

1128

1.21 1121

1172

1.26 1160

1219

1.31 1198

1266

1.36

-

-

-

-

-

-

2400

1120

1231

1.32 1159

1276

1.37 1198

1322

1.42

-

-

-

-

-

-

-

-

-

2500

1159

1340

1.44 1198

1384

1.48

-

-

-

-

-

-

-

-

-

-

-

-

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

1

0.8

0.9

1.0

1.1

1.2

1.3

RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000

940

541

0.58

980

579

0.62 1019

613

0.66 1059

641

0.69 1099

662

0.71 1140

674

0.72

1100

961

582

0.62 1000

621

0.67 1040

654

0.70 1080

682

0.73 1120

703

0.75 1161

715

0.77

1200

983

624

0.67 1022

663

0.71 1062

697

0.75 1101

725

0.78 1142

745

0.80 1182

758

0.81

1300

1006

669

0.72 1045

708

0.76 1085

742

0.80 1125

770

0.83 1165

791

0.85

-

-

-

1400

1030

718

0.77 1070

757

0.81 1109

791

0.85 1149

819

0.88 1190

840

0.90

-

-

-

1500

1057

772

0.83 1096

811

0.87 1136

845

0.91 1176

873

0.94

-

-

-

-

-

-

1600

1084

831

0.89 1124

870

0.93 1163

904

0.97 1203

932

1.00

-

-

-

-

-

-

1700

1113

896

0.96 1153

935

1.00 1192

969

1.04

-

-

-

-

-

-

-

-

-

1800

1144

966

1.04 1183

1005

1.08

-

-

-

-

-

-

-

-

-

-

-

-

1900

1175

1042

1.12

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2000

1209

1123

1.20

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2100

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2300

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2400

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK56 blower sheave and A36 belt.

Advertising