TABLE 25: PHYSICAL DATA

MODELS

BP

036

048

060

072

EVAPORATOR

BLOWER

Centrifugal Blower (Belt Drive) (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

12 x 11

Centrifugal Blower (Direct Drive) (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

12 x 10

Fan Motor HP (Direct Drive)

3/4

1

1

1

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

1 1/2

1 1/2

EVAPORATOR

COIL

Rows Deep

3

4

4

4

Fins Per Inch

13

13

13

13

Face Area (Sq. Ft.)

5.1

5.1

5.1

5.1

CONDENSER

FANS

Propeller Dia. (in.)

24

24

24

24

Fan Motor Hp

1/2

1/2

1/2

1/2

Nom. CFM

4200

4200

4200

4200

CONDENSER

COILS

Rows Deep

2

2

2

2

Fins Per Inch

18

18

18

18

Face Area (Sq. Ft.)

17.1

17.1

17.1

17.1

COMPRESSOR

Quantity

1

1

1

1

Type

Reciprocal

Reciprocal

Scroll

Scroll

AIR

FILTERS

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

1

Total Face Area (sq. ft.)

6.3

6.3

6.3

6.3

CHARGE

Refrigerant 22 (lbs./oz.)

11/12

12/8

13/4

12/0

TABLE 26: ELECTRIC HEAT CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

208

208

0.75

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 27: VOLTAGE LIMITATIONS

1

1. Utilization Range “A” in accordance with ARI Standard

110.

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-1-60

187

253

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

506