York E*BD-(T User Manual

Page 14

Advertising
background image

246819-BTG-H-0208

14

Unitary Products Group

CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.

HEATING PERFORMANCE - Upflow Furnace Coils

UNIT

MODEL*

COIL

1

MODEL

ARI HEATING

2

47

°F

17

°F

HSPF

MBH

COP

KW

MBH

COP

KW

STD

EABD-F018S

FC/MC/PC/UC18

18.0

3.62

1.46

10.5

2.28

1.35

8.00

HC18

17.9

3.60

1.46

10.4

2.28

1.34

8.00

EABD-F024S

FC/MC/PC/UC24

23.0

3.44

1.96

13.1

2.30

1.67

8.00

FC/MC/PC/UC30

23.0

3.44

1.96

13.1

2.30

1.67

8.00

HC30

23.0

3.42

1.97

13.0

2.28

1.67

8.00

HD24

23.0

3.44

1.96

13.1

2.30

1.67

8.00

EABD-F030S

FC/MC/PC35

30.0

3.66

2.48

16.2

2.22

2.14

8.00

FC/MC/PC/UC/42

30.0

3.66

2.48

16.2

2.22

2.14

8.00

HC36

30.0

3.66

2.48

16.1

2.22

2.12

8.00

HD36

30.0

3.66

2.48

16.2

2.22

2.14

8.00

EABD-(T,W)030S

FC/MC/PC35

29.0

3.66

2.32

15.7

3.66

1.25

8.00

FC/MC/PC/UC/42

29.0

3.66

2.32

15.7

3.66

1.25

8.00

HC36

29.0

3.66

2.32

15.6

3.66

1.24

8.00

HD36

29.0

3.66

2.32

15.7

3.66

1.25

8.00

EABD-F036S

FC/MC/PC35

34.4

3.44

2.93

20.4

2.50

2.39

8.40

FC/MC/PC/UC/42

34.4

3.44

2.93

20.4

2.50

2.39

8.40

FC/MC/PC/UC/48

36.0

3.86

2.73

22.4

2.78

2.36

9.00

HC42

35.8

3.86

2.72

22.4

2.78

2.36

9.00

HD36

36.0

3.86

2.73

22.4

2.78

2.36

9.00

EABD-(T,W)036S

FC/MC/PC35

34.0

3.66

2.72

20.2

3.66

1.61

8.00

FC/MC/PC/UC/42

34.0

3.66

2.72

20.2

3.66

1.61

8.00

FC/MC/PC/UC/48

35.0

3.66

2.80

21.8

3.66

1.74

8.00

HC42

35.0

3.66

2.80

21.9

3.66

1.75

8.00

HD36

36.0

3.66

2.88

22.4

3.66

1.79

8.00

EABD-F042S

FC/MC/PC/UC48

42.0

3.62

3.40

25.0

2.56

2.86

8.50

HD48

41.5

3.62

3.36

25.0

2.56

2.86

8.50

EABD-(T,W)042S

FC/MC/PC/UC48

41.0

3.66

3.28

24.4

3.66

1.95

8.00

HD48

40.5

3.66

3.24

24.4

3.66

1.95

8.00

EABD-F048S

FC/MC/PC/UC60

48.0

3.50

4.02

29.6

2.34

3.71

8.00

HC60

48.0

3.50

4.02

29.6

2.34

3.71

8.00

HD60

48.0

3.50

4.02

29.6

2.34

3.71

8.00

MC61

48.0

3.50

4.02

29.6

2.34

3.71

8.00

EABD-(T,W)048S

FC/MC/PC/UC60

47.0

3.66

3.76

29.0

3.66

2.32

8.00

HC60

47.0

3.66

3.76

29.0

3.66

2.32

8.00

HD60

47.0

3.66

3.76

29.0

3.66

2.32

8.00

MC61

47.0

3.66

3.76

29.0

3.66

2.32

8.00

EABD-F060S

FC/MC/PC/UC60

58.0

3.52

4.83

35.0

2.32

4.42

8.00

HC60

57.5

3.50

4.81

34.8

2.30

4.43

8.00

HD60

58.0

3.52

4.83

35.0

2.32

4.42

8.00

MC61

58.0

3.52

4.83

35.0

2.32

4.42

8.00

EABD-(T,W)060S

FC/MC/PC/UC60

57.0

3.66

4.56

34.4

3.66

2.75

8.00

HC60

56.5

3.66

4.52

34.2

3.66

2.73

8.00

HD60

57.0

3.66

4.56

34.4

3.66

2.75

8.00

MC61

57.0

3.66

4.56

34.4

3.66

2.75

8.00

1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and

no supplemental electric heat operation.

Advertising
This manual is related to the following products: