York E*BD-(T User Manual

Page 22

Advertising
background image

246819-BTG-H-0208

22

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

*

= Single-phase outdoor units only.

*

= Single-phase outdoor units only.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

EABD-F042S, EABD-(T,W)042S**

INDOOR COIL MODEL NO.

FC/MC/PC/UC48

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

1200

1400

1600

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

38.3

43.6

41.6

46.5

49.4

40.5

44.8

42.8

47.6

50.2

42.7

46.1

44.0

48.7

50.9

S.C.

38.3

36.8

30.3

31.3

24.1

40.5

39.8

32.7

33.6

25.5

42.7

42.9

35.1

35.8

27.0

K.W.

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.5

2.4

2.4

2.4

2.4

2.5

75

T.C.

37.0

41.4

39.7

44.3

47.0

39.0

42.8

40.8

45.3

47.4

41.0

44.3

41.9

46.3

47.9

S.C.

37.0

35.8

29.5

30.3

23.7

39.0

38.7

31.9

32.6

25.2

41.0

41.5

34.3

34.9

26.7

K.W.

2.6

2.6

2.6

2.6

2.7

2.6

2.6

2.6

2.7

2.7

2.6

2.6

2.6

2.7

2.7

85

T.C.

35.6

39.3

37.9

42.1

44.6

37.4

40.9

38.8

43.1

44.7

39.3

42.4

39.7

44.0

44.8

S.C.

35.6

34.8

28.8

29.3

23.4

37.4

37.5

31.1

31.6

24.9

39.3

40.1

33.4

34.0

26.5

K.W.

2.8

2.8

2.8

2.9

2.9

2.8

2.9

2.8

2.9

2.9

2.9

2.9

2.8

2.9

3.0

95

T.C.

34.2

37.2

36.0

40.0

42.2

35.9

38.9

36.8

41.0

42.0

37.6

40.5

37.6

41.6

41.8

S.C.

34.2

33.8

28.0

28.3

23.0

35.9

36.3

30.3

30.8

24.6

37.6

38.8

32.6

33.0

26.3

K.W.

3.0

3.1

3.0

3.1

3.2

3.1

3.1

3.0

3.1

3.2

3.1

3.1

3.1

3.2

3.2

105

T.C.

32.4

35.2

33.6

37.3

39.4

34.2

36.8

34.3

38.0

39.4

36.1

38.4

35.1

38.7

39.4

S.C.

32.4

32.2

26.7

27.1

21.7

34.2

34.3

28.9

29.4

23.3

35.8

36.4

31.2

31.6

24.9

K.W.

3.3

3.3

3.2

3.3

3.4

3.3

3.3

3.3

3.4

3.5

3.4

3.4

3.3

3.4

3.5

115

T.C.

30.6

33.2

31.2

34.7

36.7

32.6

34.7

32.0

35.4

36.9

34.6

36.3

32.7

36.0

37.1

S.C.

30.6

30.6

25.5

26.0

20.5

32.3

32.3

27.6

28.1

22.0

33.7

34.0

29.8

30.2

23.6

K.W.

3.5

3.5

3.5

3.6

3.7

3.5

3.6

3.5

3.6

3.7

3.6

3.6

3.5

3.6

3.7

125

T.C.

28.8

31.2

28.8

32.1

33.9

31.0

32.7

29.6

32.7

34.3

33.1

34.2

30.3

33.3

34.7

S.C.

28.8

29.1

24.3

24.8

19.2

30.3

30.4

26.3

26.8

20.7

31.7

31.7

28.4

28.9

22.2

K.W.

3.7

3.7

3.7

3.8

4.0

3.8

3.8

3.7

3.8

4.0

3.8

3.8

3.7

3.9

4.0

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
**

For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.

Air Handler

Coil

T.C.

S.C.

KW

MA14D

FC/MC48D

1.00

1.00

1.00

MA16C

FC/MC48C

1.00

1.00

1.00

AHP/SHP48

1.00

1.00

1.00

MV16C*

FC/MC48C

1.00

0.98

1.00

MV20D*

FC/MC48D

1.01

0.99

0.97

AV/SV48*

1.01

0.99

0.97

HD48

0.99

0.98

0.99

Variable Speed
Furnace *

Coil

T.C.

S.C.

KW

(F,L)L8VC20

FC/MC/PC48C

1.00

1.00

1.00

FL9(C,V)C16

FC/MC/PC48C

1.00

1.00

1.00

FL9(C,V)C20

FC/MC/PC48C

1.00

1.00

1.00

FL9(C,V)D20

FC/MC/PC48D

1.00

1.00

1.00

(F,L)L8VC20

HD48

0.98

0.98

0.98

FL9(C,V)C16

HD48

0.99

0.99

0.99

FL9(C,V)C20

HD48

0.98

0.98

0.98