Delta 1.07 VFD-D D User Manual

Page 37

Advertising
background image

Chapter 4 Parameter Settings|DD Series


4-13

Parameter

Explanation

Settings

Factory

Setting VF VFP SVC FO

C

FO

C

05.24 Door Close DC Brake

Starting Frequency

0.00~120.00Hz 0.00

○ ○ ○ ○

05.25 Door Re-open Current

Level 1

0.0~150.0% (AC drive’s rated current)

100.0 ○ ○ ○ ○ ○

05.26 Door Re-open Current

Level 1 for Acceleration
Area

100~200% (100% is Pr.05.25 setting)

150 ○ ○ ○ ○ ○

05.27 Door Re-open Current

Level 1 for Low Speed Area

0.0~150.0%(Drive’s rated current)

100.0 ○ ○ ○ ○ ○

05.28 Door Re-open Current

Level 2

0.0~150.0%(Drive’s rated current)

100.0 ○ ○ ○ ○ ○

05.29 Door Re-open Current

Level 2 for Acceleration
Area

0.0~150.0% (Drive’s rated current)

150 ○ ○ ○ ○ ○

05.30 Door Re-open Current

Level 2 for Low Speed Area

100~200%(100% is Pr.05.29 setting)

100.0 ○ ○ ○ ○ ○

05.31 Door Re-open Low Speed

Boundary

1.0~99.0%(Total door width=100%;
range between 0%~Pr.05.31 is excluded
from low speed detection area)

2.0 ○ ○ ○ ○ ○

05.32 Door Re-open Acceleration

Boundary

8.0~97.0%(Total door width =100%;
range between Pr.05.32~100% is the
acceleration area)

70.0 ○ ○ ○ ○ ○

05.33 Door Close Error

Deceleration Time

0.1~3600sec 0.4 ○ ○ ○ ○ ○

05.34 Door Re-open Detection

Time

0~10.0sec 0.2

○ ○ ○ ○ ○