After-sales servicing specifications – MITSUBISHI ELECTRIC LGH-50RSDC-E User Manual

Page 4

Advertising
background image

If you hear strange sounds, if no air is blown out or if some other

trouble occurs, switch off the power and contact your dealer. Consult

with your dealer concerning the cost of inspection or repair work.

Consult with your dealer about the after-sales services provided for this

Lossnay product.

After-sales servicing

Specifications

*

1

PB stands for “Power By-pass”.

*

2

Specifications are in 230V / 50 Hz operation. The unit operation is available with 220-240V / 50 Hz.

* The values given in the table for the noise level reflect the levels measured at a position 1.5 meters immediately below the unit in an anechoic

chamber.

* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change by timer setting.
* Temperature Exchange efficiency (%) are based on winter condition.

Model

Voltage

(v)

Line

frequency

(Hz)

Ventilate setting Fan

speed

Current

(A)

Power

consumption

(W)

Air volume

Static pressure

Temperature

Exchange

efficiency (%)

Enthalpy Exchange

efficiency (%)

Noise

(dB (A) )

Weight

(kg)

(m

3

/h)

(L/S) (mmH

2

O)

(Pa)

Heating

Cooling

LGH-50RSDC-E 230*

2

50

Lossnay Energy

recovery setting

1

1.17

165

395

110

10.2

100

77.5

71

68

31

46

2

0.67

90

305

85

6.1

60

81.5

75

72.5

26.5

3

0.35

41

215

60

3.1

30

85.5

79

77

21

4

0.20

22

144

40

1.5

15

88

82

80.5

18

5

0.13

14

90

25

0.7

7

90

84

83

18

BY-Pass

Ventilate setting

PB*

1

1.80

265

468

130

13.8

135

-

-

-

35

1

1.20

164

395

110

10.2

100

-

-

-

31

2

0.70

90

305

85

6.1

60

-

-

-

26.5

3

0.35

40

215

60

3.1

30

-

-

-

21

4

0.20

21

144

40

1.5

15

-

-

-

18

5

0.13

14

90

25

0.7

7

-

-

-

18

(1mmH

2

O=9.80665Pa)

Advertising