PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

Power MoNITorING

INSTALLATIoN GUIDe

H8186-CB

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

Installer’s Specifications

Output Type BACnet

Connection 2-wire

Baud Rate

9600, 19200, 38400

Address Range

1-63

quick install

H81xxCB Series interfaces are sold as open devices.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

1. Turn off all power to the energy meter and the equipment in which it is installed.

2. Discharge static.

3. Slide the H8186-CB into the channels on either side of the energy meter until the

male connection on the meter clicks into place.

4. Insert the communication terminal onto the RS-485 communication terminals.

5. If the demand subinterval feature is used, wire it into the end of the demand

subinterval terminal.

6. Replace the voltage terminal into the energy meter.

Product identification

H8186-CB BACnet Communications Board for H81xx Energy Meter

BACnet Communication Board

for the H81xx Energy Meter

H8186-CB

table of contents

Operation

2

Data Output Specifications

2

Product Diagram

2

Configuration

3

RS-485 Communications Setup

3

Wiring

4

Installing the H8186-CB in the Energy Meter

5

Troubleshooting

5

BACnet MAC Address Setup

6

BACnet Descriptions

7

BACnet Protocol

8