Veris Industries H81xx SERIES Install User Manual

H81xx, Power monitoring, Installation guide

Advertising
background image

Installation Guide

Power Monitoring

Z205338-0F

Page 1 of 10

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

TM

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2011 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

Always observe all National and Local Codes during installation of this
product.

Provide a disconnect device to disconnect the H81xx from the supply source.
Place this device in close proximity to the equipment and within easy reach of
the operator, and mark it as the disconnecting device. The disconnecting device
shall meet the relevant requirements of IEC 60947-I and IEC 60947-3 and be
suitable for the application. In the US and Canada, disconnecting fuse holders
can be used.
Provide overcurrent protection devices for supply conductors. Install per
national or local regulations.
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the device may be impaired.

Product Overview

The H81xx Series energy meter combines industrial-grade split-core current transformers and precision
microprocessor-based metering electronics. It can detect phase reversal, eliminating load orientation concerns. The
meter and current transformers are calibrated as a set, so the installer must match their serial numbers at the time
of installation. The H8150 provides a control power voltage range of 90-132 VAC. The H8163 and H8167 provide an
extended input control power voltage range (90-300 VAC).

The H8163 and H8167 models also have a pulse output compatible with building control systems and a phase loss
output to protect equipment. All models include a slot to install a Modbus, BACnet, or Metasys communication
board (sold separately). When equipped with this board and connected to a data acquisition system, the H8163 and
H8167 can report energy and power diagnostic variables, including kWh, kW, PF, kVAR, Volts, and Amps.

H81xx

Energy Meter

AH06 (optional mounting
bracket for small, medium,
and large CTs)

Product Identification

120 VAC - 240 VAC (nom.); 90-132 VAC L-N; Display Only Output

Amps

One CT

Two CTs

Three CTs

100 Micro H8150-0100-0-1 H8150-0100-0-2 H8150-0100-0-3
200 Mini

H8150-0200-1-1 H8150-0200-1-2 H8150-0200-1-3

300 Small H8150-0300-2-1 H8150-0300-2-2 H8150-0300-2-3
400 Med

H8150-0400-3-2 H8150-0400-3-3

800 Med

H8150-0800-3-2 H8150-0800-3-3

800 Lg

H8150-0800-4-3

1600 Lg

H8150-1600-4-3

2400 Lg

H8150-2400-4-3

120 VAC - 480 VAC (nom.); 90-300 VAC L-N; Pulse, Phase Loss, and Display Outputs

Amps

One CT

Two CTs

Three CTs

100 Micro H8163-0100-0-1 H8167-0100-0-1 H8163-0100-0-2 H8167-0100-0-2 H8163-0100-0-3 H8167-0100-0-3
200 Mini

H8163-0200-1-1 H8167-0200-1-1 H8163-0200-1-2 H8167-0200-1-2 H8163-0200-1-3 H8167-0200-1-3

300 Small H8163-0300-2-1 H8167-0300-2-1 H8163-0300-2-2 H8167-0300-2-2 H8163-0300-2-3 H8167-0300-2-3
400 Med

H8163-0400-3-2 H8167-0400-3-2 H8163-0400-3-3 H8167-0400-3-3

800 Med

H8163-0800-3-2 H8167-0800-3-2 H8163-0800-3-3 H8167-0800-3-3

800 Lg

H8163-0800-4-3 H8167-0800-4-3

1600 Lg

H8163-1600-4-3 H8167-1600-4-3

2400 Lg

H8163-2400-4-3 H8167-2400-4-3