PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

05132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Electropneumatic Transducer

EP3

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

PRODUCT IDENTIFICATION

INSTALLATION

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1. Mount the EP3 transducer using the screws provided.

2. Configure the jumpers for desired operation as shown (page 2).

3. Wire the transducer as shown in the wiring diagram (page 3).

4. Attach pressure tubing to the hose barbs. Observe MAIN and BRANCH port labels.

Use flexible 1/8” I.D. poly tubing for main and branch pneumatic connections.
Main supply pressure must not exceed 45 psig.

1.8"

(46 mm)

3.73"

(95 mm)

3.45"

(88 mm)

2.1"

(53 mm)

4.9"

(125 mm)

SIDE VIEW - DUST COVER

FRONT VIEW - DUST COVER

available

Output

0 = None
3 = Analog output:
0-10VDC or
4-20mA
(selectable)

S = Standard
C = CE
(CE versions
include cover
plate)

Feedback

3 = Pressure
Loss Alarm or
Manual Mode
Alarm

Failsafe

Option

Blank = None
2 = EP Cover
Plate

3

0 = None
1 = Vent on
power fail

EP3

US or EU

SPECIFICATIONS

Input Power

22-30VDC, 20-30VAC, 47-63 Hz, 150mA max. average, 350mA peak

Control Input

4-20mA, (0-10V, 0-5V; jumper selectable), Tri-State, PWM

Input Impedance

4-20mA, 250 Ω; 0-5/0-10V, 10 kΩ

Manual Override

Digital pushbutton adjust, switch selectable mode

Alarm Contact

100mA@30VAC/DC (Pressure loss, manual mode, jumper selectable)

Accuracy

1% F.S.; combined linearity, hysteresis, repeatability @20°C ambient

Temperature Coefficient ±0.1%/°C

Operational Temperature Range

5°C to 60°C (41° to 140°F)

Operating Humidity Range

10-90% RH, non-condensing

SCIM

523 in

3

/min@45 psi (8520 cm

3

/[email protected] kPa;)

333

in

3

/min@20 psi (5407 cm

3

/[email protected] kPa)

Supply Pressure

Minimum (0.1 psi plus user F.S. pressure), maximum (45 psig)

Control Range

User programmable zero selectable from 0-25 psi: full scale 0-25 psi

Pressure Differential

0.1 psig (supply to branch)

Pressure Indication

Electronic, 3½ digit backlit LCD

Minimum Tubing Length

15 feet*

Port Connection

1/8 i.d. poly tubing

Media Connection

Clean dry air or inert gas. Not for use with oxygen service

* For shorter tubing runs use the Veris AA45 Pneumatic Capacitor

EMC Conformance: EN 61000-6-3 Class B:2007+A1 2011, EN 61000-6-1:2007, EN 61000-3-2:2000,

EN 61000-3-3:2001

EMC Special Note: connect this product to a DC distribution network or an AC/DC power adapter

with proper surge protection (EN 6100-6-1:2001 specification requirements).