EP3

INSTALLATION GUIDE

Auto

Manual

GND

INPUT

24V

CH2

CH1/PWM

OPERATION

MODE

TRISTATE

ALARM

P-LOSS MAN

INPUT VOLTAGE

0-10V 0-5V

TRI-PULL-UP

ON OFF

OUTPUT

4-20mA 0-10V

ALARM

Tristate Timing
Network
FS Point
Zero
RUN

4-20mA
Voltage
Tristate

PWM

Network

Control

SETTING

INPUT

+

-

Subtrac

t

Pressure

Add Pressur

e

4-20mA

Output

0-10V

Output

CONFIGURATION

Switch/Jumper

Description

Input

User selectable slide switch: current (4-20 mA), voltage (0-5/0-10

V), Tristate, or PWM (min 0.01-0.60 sec, max 1.0-75.0 sec).

Note: the Network Control option is disabled.

Input Voltage*

If voltage input is selected, use this jumper to choose 0-5 or 0-10 V.

Tri Pull-up

If tristate input is selected, use this jumper to turn the pull-up on

or off.

Alarm

Phase loss or manual

Output

Use this jumper to select 4-20 mA or 0-10 V output (feedback status

for branch pressure.

Setting

User selectable slide switch: Tristate timing (min 1 sec; max 600 sec,

default 60 sec), FS Point (scale point user programmable 0-25 psi),

Zero (user programmable 0-25 psig), Run.

Note: the Network option is disabled.

Mode

Auto for normal operation; Manual to adjust pressure.
Set this switch last.

* EP3 accepts DC input only. To use with AC input, include a Veris AA49 Triac Adapter in series
between the input voltage and the EP3.