2 mounting, 1 installation instructions – VEGA VEGAFLEX 55K User Manual

Page 14

Advertising
background image

14

VEGAFLEX 55K

Moisture

0%

100%

0,1 m

L

Measuring range

Mounting

Lateral load

Pressure

In case of gauge or low pressure in the ves-
sel, the mounting boss must be sealed on the
thread. Use the supplied seal ring. Make
sure that the seal ring is resistant to the me-
dium.

Cable entries

When mounting outdoors, on cooled vessels
or in humid areas where cleaning is done,
e.g. with steam or high pressure, the seal of
the electrical cable entry is very important.

Use electrical cable with a round cross-sec-
tion and tighten the cable entry firmly. The
cable entry is suitable for cable diameters of
5 mm to 9 mm.

2 Mounting

2.1 Installation instructions

Lateral load

Make sure that the cable is not subjected to
strong lateral forces. Mount VEGAFLEX at a
location where no interference caused by,
e.g., stirrers, filling inlets etc. can occur.

Moisture from outside

To avoid moisture ingress, the connection
cable leading to the housing should be
looped downward (directly in front of the
cable entry), so that rain and condensation
water can drain off. This mainly applies to
outdoor mounting, in areas where moisture is
expected (e.g. by cleaning processes) or to
cooled or heated vessels.

.

Measuring range

Keep in mind that the entire length of the rod
cannot be used.