5 technical data – VEGA VEGAFLEX 55K User Manual

Page 8

Advertising
background image

8

VEGAFLEX 55K

The min. supply voltage depends on the sensor current.

0

4

22

mA

14

15

36

V

Range of the required
terminal voltage on the
sensor

Sensor current

Product description

1.5 Technical data

Power supply

Supply voltage
- two-wire sensor

24 V DC (15 … 36 V DC)

Current consumption
- two-wire sensor

max. 22.5 mA

Power consumption
- two-wire sensor

max. 810 mW

V

1000

680

500

250

0

20

22

24

26

28

30

32

34

36

15 16

18

Voltage limit
Non-Ex sensor

Voltage limit
Ex sensor

HART

®

load

Supply voltage

Measuring range

VEGAFLEX 55

0.1 ... 4 m

Output signal

4 … 20 mA current signal, load max. 500

Adjustment

- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- HART

®

handheld