4 approvals – VEGA VEGABAR 25 User Manual

Page 8

Advertising
background image

8

VEGABAR 25

1)

Relating to the nominal range.

2)

Acc. to IEC 770, item 6.1.2 relating to the nominal range.

Product description

Long-term stability

Long-term drift of the zero signal

1) 2)

< 0,25 %

Other actuating variables

Calibration position

standing, diaphragm pointing downwards

Influence of the installation position

< 5 mbar

Vibration resistance

mechanical vibrations with 4 g and

5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2

Operating conditions

Product

Aggregate condition

gas, steam, liquid up to high viscosity

also abrasive and aggressive with suitable
material selection of wetted parts
acc. to order code

Ambient conditions

Ambient temperature

-40°C … +85°C

- indicating module

-20°C … +70°C

Storage and transport temperature

-40°C … +85°C

Product temperature

-40°C … +100°C

1.4 Approvals

StEx Zone 10
Ship approval
CENELEC EEx ia IIC
ATEX II 1G EEx ia IIC and WHG
ATEX II 1G EEX ia IIC and ship approval
DVGW (applied)

If the use of approved instruments is required for certain applications, the appropriate legal
documents (test reports, test certificates and conformity certificates) must be observed.
These are supplied with the appropriate instrument.

Advertising