17

Electrical connection

Floating relay output (VIB E30 R, E40 R,
E50 R)

Power supply:
20 … 250 V AC, 50/60 Hz; 20 … 72 V DC (for
further information see Technical data)

For direct switching of external voltage sources
to relays, contactors, magnet valves, warning
lights, horns, etc.

Two-wire output (VIB E50 Z)

For connection to a VEGATOR signal condi-
tional instrument (only with VEGAVIB 51, 52 and
53)

Power supply via the connected VEGATOR
signal conditioning instrument (12 … 36 V DC)
(for further information see Technical data)

As a rule, the signal lamp in the housing lights
when the vibrating rod is immersed, independ-
ent of the mode set in the signal conditioning
instrument.

Note the operating instructions manual of the
signal conditioning instrument. Suitable signal
conditioning instruments under Technical data.

1

2

3

4

5

6

+

L1

-

N

Relay output

Power supply

-

1

2

3

4

+

5

Power supply : 10 … 55 V DC
(for further information see the following con-
nection examples as well as Technical data)

Connection examples

The transistor switches the supply voltage of the
oscillator to the binary input of a PLC or to an
electrical load. By connecting the consumer
(load) in different ways, PNP or NPN action can
be preset.

NPN action

PNP action

-

+

-

1

2

3

4

5

1

2

3

4

5

+

-

+

-

+

Floating transistor output
(VIB E40 T, E50 T)

-