VEGATRENN 548 V Ex

3

Product description

1 Product description

1.1 Function, configuration and

mounting

Function

Ex-separator VEGATRENN 548 V Ex is used
for intrinsically safe, galvanically isolated
supply of up to 15 digital (VBUS) presure
transmitters. At the input side it is connected
to the tow-wire-VBUS-line of the signal
conditioning instruent and provides at the
output side 15 intrinsically safe ia-circuits.

The Ex-separator can be used in conjunction
with the following signal conditioning
instruments or sensors:
- VEGAMET 514 V and 515 V
- EV-card of VEGALOG 571
- pressure transmitter D80, D81, D84 or D86

in Ex-version with VBUS-electronics E23V

The ia-circuits are divided into 3 branches, up
to five sensors can be connected to each
branch. The ia-circuits are galvanically
connected and a fuse per branch is used for
safety reasons.

The intrinsically safe circuits are galvanically
isolated from the not intrinsically safe circuits.

Configuration

The Ex-separator VEGATRENN 548 V Ex is
designed in 19“-technology with 5 TE (=
25,4 mm). The connection is made via a multi-
ple plug acc. to DIN 41 612.

Mounting

There are the following mounting possibilities:
- in housing type 506 with VEGAMET
- in carrier BGT 596 Ex with VEGAMET
- in carrier BGT LOG 571 *

)

with VEGALOG

Example 1:
In housing type 506 with VEGAMET

Fig. 1.1: Block diagram of the Ex-separator

Power supply

Intrinsically safe ia-
circuits

Branch 1

Branch 2

Branch 3

Signal
conditioning
instrument
(VBUS)

Electronics

VEGAMET

515V

VEGATRENN

548VEx

Not-Ex-area

Ex-area

VBUS ia IIC-
circuits

Supply

VEGATRENN
548 V Ex

VEGAMET
514 V
515 V

*) If several VEGATRENN 548 V Ex are used, it is

recommended to separate them into the cheaper
BGT 596 Ex.