2 technische daten, 2 technical data – VEGA VEGATRENN 548 V Ex User Manual

Page 5

Advertising
background image

VEGATRENN 548 V Ex

5

Product description

1.2 Technical data

Power supply

Operating voltage

U

nenn

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

approx. 4 W, approx. 6 VA

Fuse

1 A, slow-blow

Signal conditioning instrument circuit

For connection to

signal conditioning instrument VEGAMET 514 V,
515 V or EV-card of VEGALOG 571

Input voltage

U

nenn

= 25 V DC with VEGAMET
= 24 V DC with EV-card VEGALOG

The signal conditioning instrument circuit must only be connected to instruments with an
operating votlage less than 250 V.

Sensor circuit

Number

3 branches with 5 sensor current circuits each

Sensors

hydrostatic pressure transmitter with
electronics type B (VBUS)

Voltage

at 5 mA approx. 15 V DC, at 25 mA approx.
13,5 V DC

Current limitation

at approx. 30 mA, shortcircuit proof

Fuse

per circuit 1 fuse 40 mA, slow-blow

Connection line

2-wire (standard line) *

)

Resistance per conductor

max. 15

Line length

max. 1000 m

Sensor circuits, Ex-technical data

Classification

[EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC, [EEx ib] IIB

Max. values (per branch)
- voltage

U

O

- 18,2 V

- current

I

O

- 270 mA

- efficiency

P

O

- 926 mW

Characteristics

linear

EEx ia IIC

EEx ia IIB

EEx ib IIC

EEx ib IIB

Max. permissible outer inductance L

a

0,41 mH

1,8 mH

0,41 mH

1,8 mH

Max. permissible outer capacitance C

a

83 nF

384 nF

290 nF

1300 nF

The intrinsically safe sensor current circuits are reliably galvanically isolated from the not
intrinsically safe circuits up to a peak value of the nominal voltage of 375 V.

Indicating elements

LED in front plate

green on: operating voltage on

*

)

screened cable is recommended for electromagnetic interferences.

Advertising