VEGATOR 537 Ex

23465-EN-030723

Inputs

Number

2 sensor inputs

Data transmission

analogue

Switching threshold

12 mA

Current limitation

24 mA (permanently short-circuit proof)

Sensor supply voltage

15 … 18 V DC

Connection cable

2-wire

Resistance per conductor

max. 35

Integration time

0.2 … 20 s, directionally switchable
(adjustment via DIL switch)

Relay output

Number, function

2 switching relays (spdt), 1 fail safe relay

Mode

A/B-mode
A - max. detection or overfill protection
B - min. detection or dry run protection

Contact

1 spdt each

Contact material

AgCdO and Au plated

Turn-on voltage

min. 10 mV
max. 250 V AC, 250 V DC

Switching current

min. 10 µA
max. 3 A AC, 1 A DC

Breaking capacitance

max. 500 VA AC, 54 W DC

Transistor output

Number, function

3, synchronously switch with relays

Galvanic isolation

floating

Max. values

U

B

max. 36 V DC

I

B

max. 60 mA

Transistor voltage loss

U

CE

min. - 1.5 V at I

B

60 mA

Blocking current

< 10 µA

Indicating elements

LED in front plate
- green on

operating voltage on

- yellow

switching point control

- red

fault signal

Explosion protection

Certificate

conformity certificate
TÜV 01 ATEX 1780

Classification mark

ATEX II 1 GD EEx ia IIC/IIB

Please note the attached saftey instructions containing important information on installation
and operation in Ex areas.
These safety instructions are part of the operating instructions manual and come with the
Ex approved instrument.