3 communication structure, 3communication structure, Addressing of the measured value – VEGA VEGASCAN 850 Modbus signal output User Manual

Page 5

Advertising
background image

Modbus signal output VEGASCAN 850

5

0

30001

2

30003

4

30005

6

30007

8

30009

10

30011

12

30013

14

30015

504

30505

506

30507

508

30509

16

30017

4 Byte

Register
address

in

Modicon

DCS output 2

DCS output 1

DCS output 3

DCS output 4

DCS output 5

DCS output 6

DCS output 7

DCS output 8

DCS output 9

DCS output 58

DCS output 59

DCS output 60

High-

Byte

Low-

Byte

Unit

Sta-

tus

Meas. value

Add. info

Register

address in
VEGASCAN

850

Addressing of measured values

Addressing of the measured value

The measured value image is always sorted
according to DCS outputs. The following
illustration shows the addressing of the inter-
mediate storage via Modbus.

Note:

A complete overview on the process image
of the measured values of VEGASCAN 850 is
given in chapter "1.7 Measured value image“.

3

Communication structure

Within the data communication between
VEGASCAN 850 and the connected process
data processing, the following functions are
supported:
- Mode (VEGASCAN 850 is Slave)
- Instrument address (default value # 1)
- Enquiries:

Function 01, Read Coil Status
Function 02, Read Input Status
Function 04, Read Input Register(s)

- Diagnostic

Function 08, Loop back Diagnostic

The RTU mode or the ASCII mode are used
as transmission mode.

Here, each DCS value transmitted by
VEGASCAN is represented by one register
address (= 2 register words = 4 Byte):
- 2 Byte indication value
- 1 Byte unit of measurement (is filled with 0)
- 1 Byte status information

The decimal point as well as the measure-
ment unit of the DCS value are transferred by
VEGASCAN to the Modbus.

This information must be completed by the
user with the software of the process data
processing.

Contents enquiry telegram
(Modbus master –> VEGASCAN 850):

• Instrument address VEGASCAN on Mod-

bus

• Function code
• Address of the 1. register (Modicon regis-

ter memory)

• Number of registers
• Check sum (error control)

Contents answer telegram
(VEGACOM 557 –> Modbus master):

• Instrument address VEGASCAN on Mod-

bus

• Function code
• Number of register data bytes
• Register data
• Check sum (error control)

Communication structure