1application and function, 2technical data – VEGA 9130 Safety barrier User Manual

Page 2

Advertising
background image

2

Safety barrier type 9130

1

Application and function

Safety barrier type 9130 is a passive compo-
nent. It converts a not-intrinsically safe circuit
without galvanic isolation into an intrinsically
safe circuit.

The term „intrinsically safe“ characterizes a
circuit in which the energy flow is limited and
capacitive as well as inductive energy storage
is saved such that neither switching com-
mands nor shortcircuits can ignite an explo-
sive mixture.

Safety barrier type 9130 takes over this func-
tion. It limits the energy flow, damps the ca-
pacitance C

a

and the inductance L

a

of the

output circuit and reduces the saved energy
reliably. The saved circuits cannot ignite ex-
plosive mixtures.

Operating instruction

Example:

An indicating instrument is mounted in Ex-area
and requires an intrinsically safe 0 … 20 mA-
current signal.

The existing 0 … 20 mA-signal to the indicat-
ing instrument however is not intrinsically safe.

Safety barrier type 9130 is connected to the
signal line to supply the indicating instrument
in Ex-area with an intrinsically safe 20 mA-
signal. The safety barrier then provides on its
output an intrinsically safe 0 … 20 mA-current
signal for the indicating instrument.

Note:

The capacitance C

a

and inductance L

a

of the

output circuit out of the indicating instrument
and the supply line must not exceed the
stated limit values. The standard wiring is
normally within these values.

2

Technical data

General

Mounting place

outside Ex-area on C-rail

Operating temperature

-20°C … +40°C

Storage and transport temperature

-40°C … +75°C

Cross-section area of conductor

1,5 mm

2

(terminals)

Protection
- terminals

IP 20

- housing

IP 40

Weight

100 g

Approvals

PTB-no. Ex-91.C.2046 X

Classification

[EEx ia] II C / [EEx ia] II B

Input circuit

Nominal voltage U

N

6 V DC

Zener voltage

8,6 V

Min. series resistance

R

min

64

Max. series resistance

R

max

73

Leakage current against earth at U

N

1 µA

Output circuit

Short circuit current I

K

128 mA

Capacitance C

a

at EEx ib IIC

7 µF

Inductance L

a

at EEx ia IIC

1,3 mH

Capacitance C

a

at EEx ib IIB

70 µF

Inductance L

a

at EEx ib IIB

7 mH

Advertising