4mounting, 3dimensions 5 electrical connection – VEGA 9130 Safety barrier User Manual
Page 3
Safety barrier type 9130
3
3
4
1
2
9001/01-
086/150/10
160
+
–
+
–
+
–
Operating instruction
4
Mounting
• Plug the safety barrier outside the hazard-
ous area to a C-rail.
• Connection the potential equalization line out
of the Ex-area to the PA-terminal.
• Connect the intrinsically safe circuit (blue)
correctly to position on the safety barrier
which is marked blue. Note the polarity.
• Now connect the not-intrinsically safe circuit
correctly to the upper side (white) of the
safety barrier. Wrong polarity destroys the
safety barrier.
Note:
Lines in Ex-areas must be marked blue along
their entire length.
Not Ex-area
Ex-area
3
Dimensions
5
Electrical connection
U
N
0 … 20 mA-input
circuit (not intrinsi-
cally safe)
0 … 20 mA-output
circuit (intrinsically
safe)
e.g. indicating instru-
ment