5.3 Failure rectification

Failure

Rectification / Measure

Instrument is dead /
Green operating
control lamp
extinguishes

Check the voltage supply and the mains connections as described
under “Connection instructions“ on page 8. If the instrument still
does not function, please call our service department.

Red failure LED
lights

Check the sensor inputs for the following failures:
- short circuit on the input
- sensor not connected correctly or polarity-reversed

- sensor line interrupted
- supply voltage too low

Check if the sensor is connected correctly

- failures in the sensor, effecting a current change to below 2 mA or

above 23 mA, generate a fault signal on VEGATOR.

Measure the current in
the connection cable to
the sensor.

For Ex systems, make sure that the Ex protection is not de-
graded by the measuring instruments.

28

30

32

+

-

+

±

+

-

mA

V

4 … 20 mA

12 … 20 V

VEGATOR

Sensor