3 technical data – VEGA VEGABAR 15 User Manual

Page 4

Advertising
background image

4

VEGABAR 15

Product description

1.3 Technical data

Power supply

Supply voltage

10 … 30 V DC

Permissible residual ripple

U

SS

£ 1 V

Max. permissible load

depending on the supply voltage
(see load diagram)

10

500

1000

15

20

25

30

0

Load R

Ltotal

in Ohm

Supply voltage U

H

in Volt

Output signal

The analogue 4 … 20 mA output signal (measuring signal) is transmitted together with the
power supply via one two-wire cable.
Range

3.5 … 23 mA

Current limitation

approx. 28 mA

Accuracy

1)

(typical values under reference conditions, all statements relate to the nominal

measuring range)

Determination of characteristics

limit point adjustment acc. to DIN 16 086

Characteristics

linear

Deviation in characteristics
- inner sensor element

< 0.3 %

- flush version

< 0.2 %

Hysteresis

< 0.1 %

Repeatability

< 0.1 %

Average temperature coefficient of the
zero signal

2)

< 0.2 %/10 K

Long-term drift of the zero signal

< 0.25 % per year

Calibration position

upright, diaphragm points downwards

Vibration resistance

mechanical vibrations with 4 g and

5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2

Characteristics

Delay time (0 … 63 %)

< 4 ms

Ambient conditions

Ambient temperature

-40°C … +85°C

Storage and transport temperature

-50°C … +85°C

Product temperature

-40°C … +100°C