Current consumption of all sensors [mA]
The current consumption of all connected sensor types must
be added together. The max. cable length [m] is shown in the
diagrams.
VEGA sensor type
Current consumption
VEGASON
51P … 53P
54P … 56P
61 … 63
64, 65 (four-wire)
10 mA; ±1 mA
45 mA with U
Terminal
=
24 V
10 mA, ±0.5 mA
10 mA, ±0.5 mA
VEGAPULS
51P … 54P
42P … 45P
61 … 68
10 mA; ±1 mA
10 mA; ±1 mA
10 mA, ±0.5 mA
VEGAFLEX
51P, 52P
61 … 67
10 mA; ±1 mA
10 mA, ±0.5 mA
VEGABAR
40 … 44
52 … 54
61 … 67
10 mA; ±1 mA
10 mA, ±0.5 mA
10 mA, ±0.5 mA
D series
D
90 … D97
10 mA; ±1 mA
VEGACAL
62 … 66
10 mA, ±0.5 mA
VEGACAP
11.5 mA; ±1 mA
Cable lengths with PA reference cable type A (44 Ohm/km;
0.8 mm)
10
110
210
310
410 510 610
710
810
910
0
200
400
600
800
1000
1200
970
1
2
Fig. 4: Cable length in non-Ex area
1
Max. cable length in m
2
Current consumption of all connected sensors in mA
16
VEGALOG
571 EP (Ex) - Input card Profibus PA
Connecting to power supply
25681
-EN