16

5 Connecting to power supply

VEGATRENN 149A Ex • Ex-separator for 4 … 20 mA/HART

24816-01-131025

Sensor circuit (Ex area)

The sensor must be connected to the blue

connection terminals I+ and I-. The sensor

circuit of the separator VEGATRENN 149A Ex is

separated from the processing circuit.
The sensor circuit is active, this means that the

connected sensor is powered by VEGATRENN

149A Ex.

I -

I +

+

-

I

+

I

1

2

Abb. 9: Connection sensor circuit
1 Ex area

2 Non-Ex area

Processing circuit (non-Ex area)

Processing systems such as e.g. an indicating

instrument or a PLC system are connected to

terminals O+/O-/O+H.
If a HART handheld or an interface adapter VE-

GACONNECT is connected to the communica-

tion sockets in the front, the processing system

must be connected to terminals O+H and O-.

The resistance necessary for HART commu-

nication is already integrated in VEGATRENN

149A Ex with this version. Keep in mind that

in this case the max. connectable load or load

resistance is reduced (see "Technical data" in

the "Supplement").

0-

0+

Hart

0+H

0

+

0

OK

VEGADIS 175

Abb. 10: Connection example with HART communi-

cation

0+

0-

0+H

0

+

0

OK

VEGADIS 175

Abb. 11: Connection example without HART commu-

nication

5.3 Wiring plan

Terminal assignment

0+

0+

Hart

0 –

on

CONNECT

I –

I +

0–0+

I

+

I

0+H

N/–

L/+

+

L/+

N/–

1

2

3 4

Abb. 12: Wiring plan VEGATRENN 149A Ex
1 Sensor circuit

2 HART communication socket

3 Processing circuit

4 Voltage supply

Designation Terminal assign-

ment

Input and

output

L/+

L (AC), + (DC)

Voltage supply

N/-

N (AC), - (DC)

Voltage supply

Grounding

Protective conduc-

tor PE

Voltage supply

O+
O-
O+H

Measuring signal +
Measuring signal -
Measuring signal +

with HART resistor

Measuring sig-

nal processing

circuit "Non-Ex

area"