2

Ex-separator type 3041

Application and function

Ex-separator type 3041 for intrinsically safe power
supply of two-wire transmitters in Ex-areas.

Transmitters such as e.g. VEGABAR and VEGADIF,

with a current output of 4 … 20 mA, are used in
conjunction with the separator in Ex-areas. The
separator separates Ex-areas from not-Ex-areas,
meets Ex ia IIC and is characterized by three general
functions:

- intrinsically safe power supply of a two-wire

transmitter in Ex-areas

- transmission of the 4 … 20 mA current signal
- galvanic isolation of the three circuits (power

supply, converter and output circuit).

The power supply of 20 … 35 V DC is connected to
terminals 3 and 4..

On terminals 5 and 6 the separator delivers an

intrinsically safe, floating DC voltage to power a two-
wire transmitter. The transmitter converts a parameter,
e.g. a pressure into a 4 ... 20 mA current signal propor-
tional to the parameter.

Operating instruction

This current signal in the trnasmitter circuit is
transmitted floating by the separator via terminals 1
and 2 to the connected signal conditioning instrument.

Due to the complete galvanic isolation of the three

circuits, the circuits can be earthed at one end to the
earth potential in any position. Problems in the signal
transmission to processing systems by earthing
problems and current loss are thereofre solved.

„Intrinsically safe“ identifies a protection by which
current and voltage of a circuit are limited such that
the energy released in case of shortcircuits and
switching procedures is not sufficient to ignite explosi-
ve mixtures.

Technical data and dimensions

Power supply (terminals 3 and 4)

Voltage

20 … 35 V DC

Power consumption

max. 2,8 W

Current consumption

max. 125 mA

Transmitter circuit (Ex-area, terminal 5 and 6)

Signal transmission range

4 … 20 mA

Characteristic for intrinsic safety (Ex ia IIC)

U

max

= 28 V; I

K

93 mA

R

I

300

; P

K

2,6 W

No-load voltage

28 V

Full load voltage

17,5 V

17,5 V – (min. transmitter operating voltage)

Line impedance max. in Ohm

Z

max

= ––––––––––––––––––––––––––––––––––––––––––––

0,023 A

Output circuit (Not-Ex-area, terminal 1 and 2)

Signal transmission areas

4 … 20 mA

Inner resistor

> 1 M

Load resistor

max. 800

Linearity error at 20

°

C

< 20

µ

A

Temperature drift

< 1

µ

A/

°

C

Residual ripple

< 10

µ

A peak – peak

Transmitters

(Sensors)

Signal

conditioning

instrument

p

in

out