Mounting and electrical connection, Operating instruction, Mounting – VEGA 3041 Ex-separator User Manual

Page 3: Connection

Advertising
background image

Ex-separator type 3041

3

Operating instruction

75

110

25

5 6 7 8

1 2 3 4

FUSE

3

82

Further data

Galvanically isolated separation between the circuits
up to a voltage of

250 V AC

Operating temperature

-20

°

C … +60

°

C

Storage and transport temperature

-40

°

C … +80

°

C

Max. cross-section area of conductor

4 mm

2

Mounting

in not-Ex-area 35 x 7,5 mm rail or screwable on two
extractable clips (therefore remove clip springs)

Fuse

125 mA slow-blow, 5 mm ø x 20 mm

Weight

200 g

Dimensions

W x H x D = 25 x 75 x 110 mm

Mounting and electrical connection

Please note:
• The DIN and VDE-regulations.
• The connection lines from the separator and

transmitter must be permanently marked.

• Do not mount the separator in hazardous areas

(not-Ex-area).

• Only connect one transmitter to a separator.
• Earth the cable screenings only at one cable end..

Mounting

Plug the separator on the C-rail or screww to the base

on the extractable clips.

Connection

Connect the transmitter located in the Ex-area to the
blue coloured terminals 5 (+) and 6 (–) of the
transmitter. If strong electromagnetic interferences
have to be expected, screened cable must be used.

Connect the output circuit to the signal conditioning
instrument to the terminals 1 (+) and 2 (–). Now
connect the voltage supply with 20 … 35 V DC to
terminals 3 (+) and 4 (–).

The separator now powers the transmitter with
intrinsically safe voltage and transmits the 4 … 20 mA-
signal floating from the transmitter to the signal
conditioning instrument.

+

+

+

5 6 7 8

1 2 3 4

FUSE

Ex-area

Not-Ex-
area

Power supply
20 … 35 V DC

Signal

conditioning
instrument

Transmitter

C-rail

p

in

out