VEGA VEGATOR 631 Ex User Manual
Page 30
Turn-on voltage
≥
10 mV DC, ≤ 253 V AC/DC
Switching current
≥
10 µA DC, ≤ 3 A AC, 1 A DC
Breaking capacity
≤
750 VA, ≤ 54 W DC
Transistor output
Number, function
1 output, synchronously switching with the relay
Galvanic separation
Floating
Maximum values
-
U
B
36 V DC
-
I
B
≤
60 mA
Transistor voltage loss (U
CE
)
approx. 1.5 V at I
B
60 mA
Inverse current (I
0
)
≤
10 µA
Ambient conditions
Ambient temperature
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature
-40 … +70 °C (-40 … +158 °F)
Electromechanical data
Screw terminals
for wire cross-section up to 1.5 mm² (AWG 16)
Electrical protective measures
Protection class
-
Signal conditioning instrument
IP
30
-
Terminal socket
IP
20
Overvoltage category
II
Protection class
II
Electrical separating measures
reliable separation (VDE 0106, part 1) between
power supply, sensor input, level relay and tran-
sistor output
Approvals
1
)
ATEX
ATEX II (1) G [EEx ia] IIC
Others
WHG
Ship approval
1)
Deviating data in Ex applications: see separate safety instructions.
30
VEGATOR
631 Ex • Signal conditioning instrument
9 Supplement
23440
-EN
-090130