VEGA VEGATOR 631 Ex User Manual

Page 30

Advertising
background image

Turn-on voltage

10 mV DC, ≤ 253 V AC/DC

Switching current

10 µA DC, ≤ 3 A AC, 1 A DC

Breaking capacity

750 VA, ≤ 54 W DC

Transistor output

Number, function

1 output, synchronously switching with the relay

Galvanic separation

Floating

Maximum values

-

U

B

36 V DC

-

I

B

60 mA

Transistor voltage loss (U

CE

)

approx. 1.5 V at I

B

60 mA

Inverse current (I

0

)

10 µA

Ambient conditions

Ambient temperature

-20 … +60 °C (-4 … +140 °F)

Storage and transport temperature

-40 … +70 °C (-40 … +158 °F)

Electromechanical data

Screw terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Electrical protective measures

Protection class

-

Signal conditioning instrument

IP

30

-

Terminal socket

IP

20

Overvoltage category

II

Protection class

II

Electrical separating measures

reliable separation (VDE 0106, part 1) between
power supply, sensor input, level relay and tran-
sistor output

Approvals

1

)

ATEX

ATEX II (1) G [EEx ia] IIC

Others

WHG

Ship approval

1)

Deviating data in Ex applications: see separate safety instructions.

30

VEGATOR

631 Ex • Signal conditioning instrument

9 Supplement

23440

-EN

-090130

Advertising