Set-up

Note:
- A modification of zero does not influence

the adjusted span.

- By pushing the “+“ and “–“-keys the output

current remains on the last value, after
saving with the “OK“-key, the output cur-
rent takes the adjusted value.

Processing

Adjustment of the integration time

For damping of pressure shocks an
integration time t

i

of 0 s … 10 s can

be adjusted with the “+“ or “–“-key.

With the “OK“-key the adjusted value can be
saved.

Selection of the unit

In the measured value indication
the actually measured pressure is
displayed on the DOT-matrix. The
appropriate unit can be chosen out
of a list with the “+“ or “–“-key and
the “OK“-key. When choosing the
unit “Scal.“ the following menu
points are available.

Scaling

In operating condition the actually measured
pressure is displayed on the indicating mod-
ule as 4-digit digital value.

The bar graph relates to the adjusted meas-
uring range and change proportionally to the
current output. Digital values < –10 % or
> 110 % are displayed as flashing figure.

By scaling user specific figures as 4-digit
digital values are coordinated on the indicat-
ing module to the values 4 mA or 20 mA of
the current output.

Outputs

Current output/Selection of the character-
istics

The current output provides the actually
measured pressure as analogue current
signal 4 … 20 mA relating to the adjustment.

The characteristics can also be
inverted, i.e. adjusted to 20 ... 4 mA
with the “+“ or “–“-key and the
“OK“-key.

Fault signal

If during the continuous self-monitoring fail-
ures, damages or interferences in the mea-
suring cell or the electronics are detected,
the fault signal is triggered via the current
output.

With the “+“ or “–“-key and the
“OK“-key you choose if the failure
current should be 22 mA or
3,6 mA.

Simulation

To check the outputs of VEGABAR
and connected components, you
can adjust with the “+“ or “–“-key an
individual pressure or %-value. The
adjusted value flashes with acti-
vated simulation. With the “OK“-key
the simulation can be finished.

ti

1

s

Simula-

tion

Sim.

xx,x

mbar

Unit

0,0

mbar

psi
kPa
%
scal.
mA

Scaling

indica-

tion

100%=

1000

Decimal

point

888,8

0%=

0

Escape

Fautl

signal

22mA

3,6mA

Current

output

4-20mA

20-4mA