VEGA VEGAPULS 45 4 … 20 mA; HART compact sensor User Manual

Page 54

Advertising
background image

54

VEGAPULS 42, 44 and 45 – 4 … 20 mA

Technical data

Parameter and measuring range

1)

Parameter

distance between product surface and process
fitting (e.g. lower flange side of the sensor)

VEGAPULS 42

- standard

ø 40 mm horn

0 … 10 m

- optional

ø 48 mm horn

0 … 15 m

ø 75, 95 mm horn

0 … 20 m

VEGAPULS 44

- DN 50, ANSI 2“

0 … 15 m

- DN 80, 100, ANSI 3“, 4“, 6“

0 … 20 m

VEGAPULS 45

0 … 4 m

Output signal

Signal output

4 … 20 mA current signal in two-wire or

four-wire technology; the HART

®

signal is

modulated to the 4 … 20 mA signal

Fault signal

current output unchanged, 20.5 mA, 22 mA
(adjustable)

Resistance/Load of the signal cable

- 4 … 20 mA two-wire

non-Ex:

max 975

Ex d ia:

max. 720

Ex ia:

max. 670

- 4 … 20 mA four-wire

500

Integration time

- analogue 4 … 20 mA

0 … 999 seconds

Two-wire technology 4 … 20 mA:
The analogue 4 … 20 mA output signal (measuring signal) is transmitted together with the
power supply via one two-wire cable.

Four-wire technology 4 … 20 mA:
Separate power supply. The analogue 4 … 20 mA output signal (measuring signal) is
transmitted in a cable separate from power supply.

Measured value display (optional)

Liquid crystal indication

- in the sensor

scalable output of measured values as graph
and number

- in the external indicating instrument

powered by the sensor

scalable output of measured values as graph

and number. The display unit can be mounted
up to 25 m away from the sensor

Adjustment

- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- HART

®

handheld

1)

Min. distance of the antenna to the medium 5 cm (only types 42 and 44)