VEGA D84 Hydrostatic pressure transmitter User Manual

Page 36

Advertising
background image

36

Pressure transmitter D84

• Click to "

Offset correction

Offset correction

Offset correction

Offset correction

Offset correction".

• When the sensor is unpressurised and in

installation position, confirm the safety
enquiry with "

OK

OK

OK

OK

OK".

You see the actual measured value from the
sensor.

• Click to "

Correct

Correct

Correct

Correct

Correct".

Setup

The example shows an absolute pressure
transmitter with a measuring range of
0 … 1000 mbar, with which low pressures
(partial vacuum) are measured. The min.
value was set to 50 mbar and the max. value
(span) to 1000 mbar (i.e. the final value of the
measuring range).

• Confirm your adjustments with "

OK

OK

OK

OK

OK" and

after a short data transmission to the
sensor, you are again in the menu window
"

Adjustment".

• Quit all menu windows with "

Quit

Quit

Quit

Quit

Quit" and you

are again in the initial menu.

Offset correction (not possible with abso-
lute pressure transmitters)

With this menu you can carry out a zero point
correction/position correction (unpressurized
sensor).

• Choose in the initial menu "

Instrument data/

Parameter adjustment" the item "Additional

Additional

Additional

Additional

Additional

functions

functions

functions

functions

functions".

Advertising