5 connecting to power supply, 1 preparing the connection, 2 connection procedure – VEGA VEGADIS 11 User Manual

Page 10: 5 c onnecting to power supply

Advertising
background image

5 C

onnecting to power supply

5

.1 Preparing the connection

Always keep in mind the following safety instructions:

l

Connect only in the complete absence of line voltage

In hazardous areas you should take note of the appropriate
regulations, conformity and type approval certificates of the
sensors and power supply units.

VEGADIS

11 is connected with standard two-wire cable

without screen.

An outer cable diameter of 5 … 9 mm ensures the seal effect
of the cable entry. If electromagnetic interference is expected
which is above the test values of EN 61326 for industrial areas,
we recommend the use of screened cable.

Take note of the corresponding installation regulations for Ex
applications.

If screened cable is necessary, connect the cable screen on
both ends to ground potential. In the VEGADIS 11, the screen
must be connected directly to the internal ground terminal. The
ground terminal on the outside of the housing must be
connected to the potential equalisation (low impedance).

If potential equalisation currents are expected, the connection
on the processing side must be made via a ceramic capacitor
(e. g. 1 nF, 1500 V). The low frequency potential equalisation
currents are thus suppressed, but the protective effect against
high frequency interference signals remains.

In Ex applications, one-sided grounding on the sensor is
recommended, see EN 60079-14.

5

.2 Connection procedure

Proceed as follows:

1

Unscrew the housing cover

2

Loosen compression nut of the cable entry

3

Remove approx. 10 cm of the cable mantle, strip approx.
1 cm insulation from the individual wires

4

Insert the cable into VEGADIS 11 through the cable entry

Note safety instructions

Take note of
safety instruc-
tions for Ex ap-
plications

Selecting connection
cable

Select connec-
tion cable for Ex
applications

Cable screening and
grounding

Cable screen and
grounding for Ex appli-
cations

10

VEGADIS

11

Connecting to power supply

19888

-EN

-080227