VEGA VEGADIS 11 User Manual
Page 15
1
2
3
Fig. 7: Indicating elements of VEGADIS 11
1
Bar graph
2
Tendency indication
3
Digital value
l
four positions as well as signa and decimal point
l
individual scaling between -9999 … +9999
The display outputs the current 4 … 20 mA as bar graph and
digital value.
With 4 mA no segment of the bar graph appears, with 20 mA
all segments appear. This assignment is fix.
You can scale the digital value to any value between -9999 …
+
9999 via the adjustment module.
To scale the indication, proceed as follows:
1
Initial value: Set rotary switch to "zero"
2
Set the requested value, e.g. 0 with the [+] and [-] keys
3
Final value: Set the rotary switch to "span"
4
Set the requested value, e.g. 1000 with the [+] and [-] keys
5
Decimal point: Set the rotary switch to "point"
6
With the [+] and [-] keys you can adjust the requested
value, e.g. 8888 (no decimal point)
7
Set rotary switch to "OPERATE"
8
Screw the housing cover on
The adjustment data are effective, the output current 4 … 20 mA
corresponds to the actual level.
Indicating elements
Adjustment steps, scal-
ing
VEGADIS
11
15
Set up
19888
-
EN
-080227