VEGA VEGABAR 64 Profibus PA User Manual

Page 53

Advertising
background image

Current value

10 mA, ±0.5 mA

Dynamic behaviour output

Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 28: Sudden change of the process variable, dead time t

T

, rise time t

A

and step response time t

S

1

Process variable

2

Output signal

Dead time

150 ms

Rise time

100 ms (10 … 90 %)

Step response time

250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Additional output parameter - temperature

Processing is made via output signal HART multidrop, Profibus PA and Foundation Fieldbus

Range

-50 … +150 °C (-58 … +302 °F)

Resolution

1 °C (1.8 °F)

Accuracy

-

in the range of 0 … +100 °C
(+32 … +212 °F)

±

3 K

-

in the range of -50 … 0 °C (-58 … +32 °F)
and +100 … +150 °C (+212 … +302 °F)

typ. ±4 K

Input variable

Adjustment

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

-

percentage value

-10 … 110 %

-

pressure value

-20 … 120 %

VEGABAR

64 • Profibus PA

53

10 Supplement