2 mounting information – VEGA VEGAVIB 67 - transistor output User Manual

Page 12

Advertising
background image

Warning:

The housing must not be used to screw in the instrument!

Applying tightening force on the housing can damage its

internal mechanical parts.
To screw in, use the hexagon above the thread.

4.2 Mounting information

Agitators, equipment vibration, etc., can cause the level switch

to be subjected to strong lateral forces. For this reason, do not

use an overly long extension tube for VEGAVIB 67, but check if

you can mount a short level switch on the side of the vessel in

horizontal position.
Extreme vibration caused by the process or the equipment, e.

g. agitators or turbulence in the vessel e.g. from fluidization,

can cause the extension tube of VEGAVIB 67 to vibrate in

resonance. This leads to increased stress on the upper weld

joint. Should a longer tube version be necessary, you can

provide a suitable support or guy directly above the tuning fork

to secure the extension tube.

This measure applies particularly to applications in Ex areas.

Make sure that the tube is not subjected to bending forces

through this measure.

If VEGAVIB 67 is mounted in the filling stream, unwanted

switching signals may be generated. Mount VEGAVIB 67 at a

location in the vessel where no disturbing influence from e.g.

filling openings, agitators etc. can occur.
This applies particularly to instrument types with long

extension tube.

Agitators and fluidization

Inflowing material

12

VEGAVIB 67 - with transistor output

Mounting

29297

-EN
-060508