5.3 Wiring plan, single chamber housing

2

3

4

1

Fig. 8: Electronics and connection compartment

1

DIL switch for mode adjustment

2

Ground terminal

3

Screwed terminals

4

Control lamp

We recommend connecting VEGAVIB 55 in such a way that

the switching circuit is open when there is a level signal, line

break or failure (safe condition).
The contactless electronic switch is always shown in non-

operative condition.
The instrument is used for direct control of relays, contactors,

magnet valves, warning lights, horns etc. It must not be

operated without an intermediately connected load, because

the electronics would be destroyed if connected directly to the

mains. It is not suitable for connection to low voltage PLC

inputs.
Domestic current is temporarily lowered below 1 mA after

switching off the load so that contactors, whose holding current

is lower than the constant domestic current of the electronics,

are reliably switched off.