VEGA VEGACAL 64 4 … 20 mA_HART - two-wire User Manual

Page 41

Advertising
background image

41

10 Supplement

VEGACAL 64 • 4 … 20 mA/HART - two-wire

30030-EN-130917

Resolution

1.6 µA

Failure signal current output (adjustable) mA value unchanged 20.5 mA, 22 mA, < 3.6 mA (adjust-

able)

Current limitation

22 mA

Load

see load diagram under Power supply

Damping (63 % of the input variable)

0 … 999 s, adjustable

Rise time

500 ms (ti: 0 s, 0 … 100 %)

Met NAMUR recommendation

NE 43

Input variable
Measured variable

level of conductive, adhesive liquids

Measuring principle

phase-selective admittance processing (PSA)

Measuring range

0 … 3000 pF

Measuring frequency

270 kHz

Accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Temperature error

Ʋ < 120 pF

< 1 pF

Ʋ > 120 pF

1 % of the current measured value

Linearity error

< 0.25 % of the complete measuring range

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

-1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig)

Process temperature VEGACAL 64 of

316L

-50 … +150 °C (-58 … +302 °F)